Detectable Combustible Gases

Gas1 Expected response at 20% LEL target gas2
Methane 20% LEL
Propane 15% LEL to 45% LEL
Butane 15% LEL to 35% LEL
Pentane 15% LEL to 45% LELg
Hexane 8% LEL to 28% LEL
Methanol/Ethanol3 6% LEL to 26% LEL
Hydrogen No response
Acetylene No response

1 For any gases not listed, please contact Honeywell Analytics to find the best solution for your application.

2 The BW Clip4 LEL sensor is optimized to see methane. While the unit can detect and respond to the other combustible gases listed in the above table, the accuracy of the readings may be in-consistent. If the primary need is to detect a specific combustible gas other than methane, please contact Honeywell Analytics to discuss an alternative product

3 Please use caution when using the BW Clip4 around Methanol and/or Ethanol. The BW Clip4 CO sensor may become inhibited by prolonged exposure to concentrations of Methanol and/or Ethanol thus causing the unit to alarm. This condition can last up to 12 hours before the CO sensor recovers to normal levels.