1-866-4 JJSTECH(1-866-455-7832)

Honeywell Analytics Searchline Excel Infrared Open Path Flammable Gas Detector, Short range TX/RX 5m to 40m UL Current Sink - 02104-N-5040

Item #:
02104-N-5040
Brand:
Honeywell Analytics
Honeywell Analytics Searchline Excel Infrared Open Path Flammable Gas Detector, Short range TX/RX 5m to 40m UL Current Sink - 02104-N-5040
$13,822.00
Qty
Send This Page to a Friend

Ask an Expert

Our tech experts are ready to help!

1-866-4 JJSTECH (1-866-455-7832)

Email Us
Share this product:
Honeywell Analytics Searchline Excel Infrared Open Path Flammable Gas Detector, Short range TX/RX 5m to 40m UL Current Sink - 02104-N-5040

Honeywell Analytics Searchline Excel Infrared Open Path Flammable Gas Detector, Short range TX/RX 5m to 40m UL Current Sink - 02104-N-5040

$13,822.00

02104-N-5040 Searchline Excel Infrared Open Path Flammable Gas Detector, Short range TX/RX 5m to 40m UL Current Sink by Honeywell Analytics

The Searchline Excel is the World's best selling infrared open path gas detector with over 25,000 units installed in challenging applications throughout industry. From the Arctic Circle to middle eastern deserts, customers have repeatedly selected the Searchline Excel as their preferred choice.

Product Evolution

Honeywell Analytics pioneered the original design of open path infrared flammable gas detectors with the introduction of the original Searchline back in 1987. Since then we have continued to work in conjunction with major international oil and gas companies to fully understand the demanding application requirements of these systems.

In 1998 we introduced Searchline Excel which has become the industry standard for open path gas detection by meeting and exceeding all customer driven demands.

With continuous improvement and the highest quality manufacturing and control processes, Honeywell Analytics Searchline Excel Open Path flammable gas detector provides best in class gas detection. Excel is often the chosen primary flammable gas detector in conjunction with Searchpoint Optima Plus as complimenting flammable point detection.

Why open path gas detection?

Open path detectors complement the use of individual point detectors and offer many significant benefits including:

  • Reliable flammable gas detection, proven in use
  • Wider area coverage - most likely to pick up any leak
  • Very high speed of response
  • Failsafe - no unrevealed failure modes - no possibility of blocked gas path to detector
  • Detector location not as critical
  • Indicates size of hazard
  • Simple set up and commission
  • Replaces multiple point devices

Applications include

  • Offshore platforms & vessels (FPSO's)
  • Downstream chemical processing plants
  • Gas transport and pipelines
  • Large storage areas & buildings
  • Perimeter detection

Features and Benefits

  • Double band pass filters that fully compensate for all types of fog, rain and/mist interference
  • 100% Solar Immune
  • Correct operation under partial obscuration conditions
  • High vibration resilience
  • Radially symmetrical and bonded window heating delivers good low temperature performance
  • Coaxial optics delivers best in class performance and resilience to partial obscuration
  • Fully temperature compensated solid state detectors
  • Low power consumption in all conditions
  • Simple 'lock on' alignment tool
  • No extra 'software alignment' required
  • Higher power and more robust design telescope
  • Optional Modbus RS485 multi drop output
  • FM hazardo
Available Gases Methane, Ethane, Propane, Butane, Pentane, Ethylene, Propylene, Butadiene
Range 0 to 5 LEL.m
Recommended Alarm Settings (Low) 1.0 LEL.m; (high) 3.0 LEL.m
Path Lengths Short Range 5m to 40m (15ft to 130ft.), Medium Range 40m to 120m (130ft to 390ft.) and Long Range 120m to 200m (390ft to 650ft.)
Speed of Response T90 less than 3 seconds. (under normal operating conditions)
Output Signal 4-20mA (maximum loop resistance 600 ohms; source & sink available) and RS485
21mA Over range
4-20mA Normal operation (0 to 5 LEL.m)
3mA(1) Dirty optics
2.5mA(1) Beam blocked
2mA(1) 0mA Fault
Digital Output Modbus RS485 multi drop. Using DX100 (M) or XNX Universal Transmitter with Modbus option
Operating Temperature -40°C to +65°C (-40°F to 150°F)
Operating Humidity 0 to 99% RH (non-condensing)
Operating Pressure 91.5 to 105.5 KPa (915 to 1055 mbar) (non-compensated)
Warm-up Time Less than 5 minutes (operational), or less than 1 hour (fully stabilised)
Power Supply 18V to 32VDC
Power Consumption Short Range Tx: 3.5W / 5.0W *maximum. Medium and Long Range Tx: 10W / 13W* maximum. Rx: 8W maximum.
Enclosure Material 316 stainless steel
Weight (inc. mounting bracket) Short Range TX: 3.5kg Medium and Long Range TX: 7kg RX: 3.5kg
Vibration 2 to 60Hz, max ptp amplitude 1mm.
Misalignment Tolerance Short Range ±0.5° (±~35cm at 40m). Medium Range ±0.5° (±~104cm at 120m). Long Range ±0.5° (±~170cm at 200m)
EMC Standards EN50270
Performance Approval FM performance approved
IP Rating IP66 and IP67

Questions & Answers