48VFL11 1/16 DIN Temperature PID Controller with One Relay Output by Extech

Extech controllers now offer Fuzzy Logic enhanced PID and a Soft-Start feature that protects heaters from cold-starts. PID plus Fuzzy Logic tackles even the most demanding applications, eliminating over-shoot, unwanted process fluctuations, and drift. The Soft Start feature is ideally suited for processes, such as those employed in the Thermo-Plastics industry, where careful, exact, and slow heating of product is required.

Features

  • Dual 4-digit LED displays for process and setpoint values
  • 1/16 DIN (48VFL) and 1/4 DIN (96VFL) model dimensions available
  • Easy programming & navigation with user-friendly menus and tactile keypad
  • Fuzzy Logic PID offers intuitive control simulating human control logic
  • Manual mode allows the user to override automatic control and drive the controller output higher or lower with the touch of a button
  • One-touch Auto Tuning for quick setup and stable, precise control
  • Two 'Latching' Alarm relays standard with 8 Alarm modes plus advanced Timer modes
  • Single stage Ramp and Soak program with Ramp-to-Setpoint Limit that can be combined with the Soft Start feature for critical process demands
  • Accepts thermocouple and RTD inputs
  • Select desired temperature display units (°F or °C) from setup menu
  • Select thermocouple input type (9 selections) or RTD input (2 selections) from the display menu without the need for hardware modification
  • Complete with mounting bracket hardware and screw terminals for easy wiring
General Specifications
Display Dual 7-segment 4-digit LED: Red digits for Process Variable (PV) and green digits for Setpoint Variable (SV)
Display range -1999 to 9999
Indicating accuracy ± (0.2% full scale + 1 digit)
Display update rate 4 readings per second
Output status indication Front panel Alarm (A1 and A2) and Control (C1 and C2) status LED's inform the user when an output switches on or off.
Out-of-range indication PV display flashes.
'No input' indication PV displays 'OPEN' when input terminals are disconnected.
Auto Tune indication Right-most decimal on the PV display flashes while the controller is in the auto tune mode.
Calibration data Stored in non-volatile memory along with user parameter edits.
Meter construction Case is ABS plastic and the front panel is drip- and dust-proof Lexan material (NEMA and IEC IP55 equivalent)
Power requirement 90 to 264VAC 50/60Hz (automatically accommodates any voltage between 90 to 264VAC)
Power consumption < 5VA
Insulation Resistance > 50MΩ
Noise rejection Common Mode: 120 dB; Normal Mode: 60 dB (typical)
Operating conditions 14 to 122°F (-10 to 50°C); 90% Relative Humidity max.
Storage temperature -4 to 140°F (-20 to 60°C)
Panel cut-out dimensions 1.77 x 1.77" ±0.02" (45.0 x 45.0mm ±0.5mm) for 48VFL
3.62 x 3.62" ±0.02" (92.0 x 92.0mm ±0.5mm) for 96VFL

Range Specifications
Thermocouple Input Specifications
Thermocouple (TC) types J, K, T, E, B, R, S, N, and C (user programmable)
Temp. Indication Accuracy <1000 degrees ±3.6F (2.0C)
>1000 degrees ±7.6F (4.0C)
TC Break protect Upscale and Downscale
Lead wire effect 0.015% / ohm
Input impedance > 10MΩ
Repeatability 0.83°C
Temperature stability 5uV/°C typical
TC Ranges Type K: -58 to 2498° F (-50 to 1370°C)
Type J: -58 to 1830° F (-50 to 1000°C)
Type B: 32 to 3272° F (0 to 1800°C)
Type T: -454 to 752° F (-270 to 400°C)
Type E: -58 to 1382° F (-50 to 750°C)
Type R: 32 to 3182° F (0 to 1750°C)
Type S: 32 to 3182° F (0 to 1750°C)
Type N: -58 to 2372° F (-50 to 1300°C)
Type C: -58 to 3272° F (-50 to 1800°C)
RTD Input Specifications
RTD type Platinum 100Ω (DIN or JIS)
RTD range -328 to 1202°F (-200 to 650°C)
Break protection Up- and down-scale
Lead wire effect 0.015° / Ohm
Repeatability 0.2°C
Analog (Linear) Input Specifications
Current Input 4 to 20mA DC (2.7Ω input impedance)
Voltage Input 1 to 5V DC (>10MΩ input impedance)
Display range -1999 to 9999 digits
Repeatability Within 1 digit
Relay and Pulse DC Output Specifications
Relay outputs SPST (dry contact) relays can switch up to 5 Amps @ 110V AC or 24VDC (for resistive loads only)
Pulsed DC outputs 0 to 24 VDC output (drives resistive loads to 250Ω max.)
Control actions Indirect or reverse acting (heating) and direct acting (cooling)
Control types ON/OFF control with Hysteresis (dead band)
Time proportioning control (for relay or pulsed DC output)
Standard proportional output (analog output)
Automatic tuning Push-button activation. Automatically tunes the proportional band and integral/derivative times.
Manual Tuning Proportional Band (Pb): 0.0 to 300.0% of Full Scale
Integral time or 'Reset' (Ti): 0 to 3000 seconds (includes anti-reset wind-up)
Derivative time or 'Rate' (Td): 0 to 900 seconds
Cycle Time: 0 to 100 seconds (set to '0' for 4-20mA output)
Hysteresis: 0.0 to 25.5% of Full Scale
ALARM Output Specifications
Alarm relay outputs SPST, dry contact relay can switch up to 3 Amps @ 110VAC; (for Resistive Loads)
Alarm modes Deviation, Absolute, and Band Alarms with dead band (Hysteresis) adjustment.
ANALOG Output Specifications
Analog output 4-20mA DC
Load limits 600Ω max.
Programming Set Cycle Time (Ct) to '0' to enable the analog output