1-866-4 JJSTECH(1-866-455-7832)

Extech PQ3470 3-Phase Graphical Power & Harmonics Analyzer/Datalogger

Item #:
EXT-PQ3470
Brand:
Extech
Extech PQ3470 3-Phase Graphical Power & Harmonics Analyzer/Datalogger
$3,329.00
Qty

Discontinued

Send This Page to a Friend

Ask an Expert

Our tech experts are ready to help!

1-866-4 JJSTECH (1-866-455-7832)

Email Us
Share this product:
Extech PQ3470 3-Phase Graphical Power & Harmonics Analyzer/Datalogger

Extech PQ3470 3-Phase Graphical Power & Harmonics Analyzer/Datalogger

$3,329.00

Discontinued


PQ3470 3-Phase Graphical Power & Harmonics Analyzer/Datalogger by Extech

Features

  • Large dot-matrix, sun-readable, graphical, backlit LCD
  • Full system analysis with up to 35 parameters: V (phase-to-phase), V (phase-to-ground); A (phase-to-ground); KW / KVA / KVAR / PF (phase); KW / KVA / KVAR / PF (system); KWH / KVAH / KVARH / PFH (system); Phase angle
  • Select 200A, 1200A Current Clamps or 3000A Flexible Current Probes (sold separately)
  • Adjustable Current Transformer CT (1 to 600) and Potential Transformer PT (1 to 1000) ratio for high power distribution systems
  • On-screen Harmonics display (1 to 50th order)
  • Simultaneous display of Harmonics and Waveform
  • Display of Waveform with peak values
  • Analysis of Total Harmonic Distortion (THD)
  • Graphic Phase diagram with 3-Phase system parameters
  • 3-phase Voltage or Current Unbalanced Ratio (VUR, AUR) and unbalanced factor
  • Capture Transient events (including dip, swell, and outage) with programmable threshold (%)
  • Log up to 30,000 readings on a removable SD memory card in Microsoft Excel® format
  • Wide sampling rate range (2 seconds to 2 hours)
  • Captured measurements can be imported directly into Excel via the SD memory card
  • Built-in Clock and Calendar
  • Easy-to-use onscreen menu
  • Easy-to-hold rugged over molded housing

Includes

  • 4 voltage leads with alligator clips
  • 8 AA batteries
  • SD memory card
  • Universal AC adaptor (100 to 240V)
  • Case
General Specifications
Circuit Custom single-chip microprocessor LSI circuit
Display LCD Size: 81.4 X 61 mm (3.2 X 2.4")
Dot Matrix backlit LCD (320 X 240 pixels)
Measurements V (voltage phase to phase)
V (voltage phase to ground)
A (Current Phase to ground)
KW / KVA/ KVAR / PF (Phase)
KW / KVA/ KVAR / PF (System)
Power factor
Phase angle
Frequency
Harmonics
Wire configurations 1P/2W, 1P/3W, 3P/3W, 3P/4W
Voltage ranges 10 ACV to 600 ACV (Auto Range)
Current ranges Current probe input signal voltage (ACV): 200mV /300mV /500mV /1V /2V /3V
Current probe input current range (ACA): 20A/200A/2000A1200A)/30A/300A/3000A/60A/600A/6000A
Note that the meter has universal probe compatibility
Safety standard IEC1010 CAT III 600 V
ACV input impedance 10M ohms
Range select ACV Auto Range
ACA Manual Range
Clamp frequency response 40 Hz to 1 KHz
Tested clamp frequency 45 to 65 Hz
Over-load protection ACV 720 ACV RMS
Over-range "OL" is displayed; ACV
Data on SD card will read '9999' or '999' for over-range data
Under-range "UR" is displayed
Data Hold Freezes displayed reading
Data Recording SD memory card
SD Card capacity 2G SD max. / 16G SDHC max.
Sampling Time Approx. 1 second (LCD) / 2000 samples per period
Datalogger Real time data logger saves data to SD memory card for download to PC (data files open directly to spreadsheet)
Sampling rate: From 2 seconds to 7200 seconds
Max. file capacity: 30,000 records
Data Output Serial or USB connection (cable supplied)
Operating Temperature 0 to 50°C (32 to 122Z°F)
Operating Relative Humidity 80% Relative Humidity max.
Power Supply Eight (8) 'AA' 1.5VDC batteries or AC 9V power adapter
Power Consumption Meter: 270 mA DC; Clamp: 22 mA DC
Max. Conductor size Clamp can accommodate up to 50 mm (2.0") diameter
Weight Meter: 1026g (2.3 lbs.) (with batteries); Clamp: 467g (1.0lbs)
Dimensions Meter: 225 X 125 X 64 mm (8.86 X 4.92 X 2.52")
Optional Clamp: 210 X 64 X 33mm (8.3 X 2.5 X 1.3")
Optional Clamp Jaw: 86 mm (3.4") Outer diameter
Accessories Included Instruction manual; Batteries; SD card (2G)

General Specifications
Function
Range
Resolution
Accuracy
AC Voltage
10.0V to 600.0V
0.1V
± (0.5% range + 3 digits)
AC Voltage (peak to peak)
28.2V to 1.697kV
0.1V to 1V
± (0.5% range + 30 digits)
AC Current (trms)
0.2A to 6000A
0.001A to 1 A
± (0.5% range + 5 digits)
AC Current (peak to peak)
2.828A to 16.97kA
0.001A to 10 A
± (0.5% range + 30 digits)
Power Factor
0.00 to 1.00
0.01
± 0.04
Φ Phase Angle
-180° to 180°
0.1°
± 1°
Frequency
45 to 65Hz
0.1Hz
0.1Hz
Power
0.0 to 3.6MW
0.001k to 0.001M
± (1% range+8 digits)
0.0 to 3.6MVA
0.0 to 3.6MVAR
Watt-Hour
0.0 to 3.6MWH
0.001k to 0.001M
± (1% range+8 digits)
0.0 to 3.6MVAH
0.0 to 3.6MVARH
Harmonics Magnitude (>5%, 50/60Hz)
Range
Resolution
Accuracy
ACV
1 to 20th
0.1V
± (2% + 5 digits)
21 to 30th
± (4% + 5 digits)
31 to 50th
Reference only
ACA
1 to 20th
0.001A to 1A
± (2% + 5 digits)
21 to 30th
± (4% + 5 digits)
31 to 50th
Reference only
Harmonics Magnitude (>5%, 50/60Hz)
Range
Resolution
Accuracy
ACV
1 to 20th
0.1%
± (2% + 10 digits)
21 to 30th
± (4% + 20 digits)
31 to 50th
Reference only
ACA
1 to 20th
0.1%
± (2% + 10 digits)
21 to 30th
± (4% + 20 digits)
31 to 50th
Reference only
Crest Factor (ACV or ACA)
1.000 to 9.999
0.001
± (5% + 0.3)
Total Harmonic Distortion
0 to 20%
0.1%
± (2% + 5 digits)
20.1 to 100%
± (6% + 10 digits)

Datasheets & User Manuals

Questions & Answers


There are no questions or answers for this item.