28145 Si-TH4 wireless temperature-hygrometer (psychrometer) probe by Sauermann

This wireless psychrometric probe provides accurate indoor and outdoor temperature and hygrometry measurements to work on air conditioning, refrigeration and heat pump installations.

The Si-TH4 calculates dry and wet bulb temperatures quickly and easily, using a flexible probe with a sliding magnet for convenient positioning. It connects easily to the Si-RM350 and Si-RM450 manifolds, as well as to the mobile application Sauermann Pilot.

  Temperature Humidity
Type of sensors CMOS CMOS
Measuring range -20 to 60°C (-4 to 140°F) 0 to 100%RH
Accuracy* -20 to 0°C (-4 to 32°F): ±0.3°C (0.6°F)
0°C to 60°C (32 to 150°F): ±0.5°C (0.9°F)
±2 %RH (from 15°C to 25°C and from 10 to 90 %RH)
±5 %RH (from 15°C to 25°C and from 0 to 10 %RH and from 90 to 100 %RH)
Temperature dependence: ±0.04 x (T-20)%RH (if T<15°C or T>25°C)
Available units °C, °F %RH
Resolution 0.1°C, 0.1°F 0.1%RH
Response time T90 60 s 60 s
Probe
Power supply 3x LR03 AAA 1.5 V alkaline batteries
Battery life 50 h @ 20°C / 68°F
Wireless frequency Range frequency from 2402 MHz to 2480 MHz with a transmission power of 8 dBm.
Wireless range Range between manifold and wireless probes up to 100 m (328 ft). App connection: depends on smartphone radio strength, range up to 100 m (328 ft).
Compatibility Smartphone minimum required versions: Android 11.0, iOS 15, BLE 5.0**
Storage temperature From -20 to 50°C (-4 to 122°F)
Environmental conditions of use In non-condensing condition Altitude: from 0 to 2000 m (0 to 6561’) Non-corrosive gases
European directives 2011/65/EU RoHS II; 2012/19/EU WEEE; 2014/53/EU RED