1-866-4 JJSTECH(1-866-455-7832)

Fieldpiece Loaded Clamp Meter - SC640

Item #:
FP-SC640
Brand:
Fieldpiece
Fieldpiece Loaded Clamp Meter - SC640
$294.00
Qty

Discontinued

Send This Page to a Friend

Ask an Expert

Our tech experts are ready to help!

1-866-4 JJSTECH (1-866-455-7832)

Email Us
Share this product:
Fieldpiece Loaded Clamp Meter - SC640

Fieldpiece Loaded Clamp Meter - SC640

$294.00

Discontinued


SC640 Loaded Clamp Meter by Fieldpiece

The SC640 clamp meter is packed with more features and measurements than any clamp meter in the HVACR industry. The loaded SC640 features lead storage, a swivel head, test lead holder, heavy duty magnetic strap, jaw flashlight, and a backlight on the dial so you can easily choose the right measurement in poorly lit spaces. Plus the SC640 hosts all the electrical measurements HVACR pros use everyday, along with features like True RMS, Inrush current, capacitance, temperature, duty cycle, and microamps DC.

The top-of-the-line SC640 clamp meter helps HVACR professionals do more everyday:

  • Volts AC/DC
  • True RMS
  • Inrush current
  • Swivel clamp
  • Magnetic strap
  • Probe storage
  • Dual display
  • Temperature F/C
  • Capacitance
  • Duty cycle %
  • 400 amps AC
  • Microamps DC
  • Frequency via leads and clamp
  • Non-contact voltage
  • 50 Mega Ohm with 0.1 resolution
  • Continuity
  • Diode test
  • Hold
  • Clamp probe holder
  • Dial backlight
  • Clamp jaw light
  • LCD backlight
  • Low battery indicator

Includes

  • SC640 Meter
  • ADLS2 Deluxe Silicone Lead Set with Gold Plated Tips and Removable Sheath
  • ATB1 Wrap Tab Type K Thermocouple
  • ASA2 Short Alligator Lead Extensions
  • Velcro Strap
  • 9V Battery
  • ANC7 Padded Case
General Specification
Display 5000 count dual display
Backlight 60 second duration with auto-off. Blue color. SC640 only.
Overrange (OL) or (-OL) is displayed
Measurement rate 3.3 times per second, nomina
Zero Automatic
Operating environment 32°F to 122°F (0°C to 50°C) at <70% relative humidity
Storage temperature -4°F to 140°F (-20°C to 60°C), 0 to 80% RH (with battery removed)
Accuracy Stated accuracy @ 73°F±9°F (23°C±5°C), <75%RH
Temperature coefficient 0.1 x (specified accuracy) per °C [0°C to 19°C (32°F to 66°F), 28°C to 50° C (82°F to 122°F)]
APO (Auto Power Off) Approx. 30 minutes
Power Single standard 9-volt battery, NEDA 1604, JIS 006P, IEC 6F22
Battery life 200 hours typical alkaline (SC620); 100 hours typical alkaline (SC640)
Low battery indication Battery icon blinks and "LO.bt" is displayed when the battery voltage drops below the operating level
Dimensions 287.5mm(H) x 79.5mm(W) x 50.0mm(D)
Weight Approx. 450g including battery
Altitude Up to 6562 ft (2000m)
Overload protection 600 VDC or 600VAC rms unless otherwise stated
Test leads Use UL listed test leads that comply to UL61010-031 rated CATIII 600V or above. Included test leads are gold-plated and have removeable safety caps.
Temperature (°F/°C)
Range -30°F to 932°F, (-35°C to 500°C)
Resolution 0.1°
Accuracy ±(1°F)* 32°F to 120°F, ±(1°C) 0°C to 49°C
±(1%+2°F) 32°F to 572°F, ±(1%+1°C) 0°C to 300°C
±(2%+6°F) -30°F to 32°F, ±(2%+3°C) -35°C to 0°C
±(2%+6°F) 572°F to 932°F, ±(2%+3°C) 300°C to 500°C
Sensor type K-type thermocouple
Overload protection 30 VDC or 30VAC rms
Non Contact Voltage (NCV)
AC Voltage Detection Range 24VAC to 600VAC (50-60Hz)
Voltage AC (VAC) (50Hz-500Hz)
Ranges 500mV, 5V, 50V, 500V, 600V
Resolution 0.1mV
Accuracy ±(1.2% + 8) 500mV range (50-60Hz)
±(1.2%+8), 5V, 50V, 500V; ±(1.5% + 8) 600V range
True RMS model SC640 only
Crest factor ≤ 3
Audio/Visual Hi-V indicato >30VAC/VDC
Input impedance >100MΩ (500mV), 10MΩ (5V), 9.1MΩ (50V-600V)
MicroAmps DC (µADC)
Ranges 500µA
Resolution 0.1µA
Accuracy ±(1.0% + 2)
Volts burden 1V
Overload Protection 600VDC or 600VAC rms
Frequency (Hz) Through Leads
Ranges 500Hz, 5kHz, 50kHz, 500kHz, 1MHz
Accuracy ±(0.1% + 5)
Resolution 0.1Hz
Sensitivity 10Hz to 1MHz: >3.5Vrms
PW >1µs
Duty Cycle Limit >30% and <70%
Duty Cycle (%)
Ranges 5%-95% (40Hz to 10kHz), 10%-90% (10kHz to 20kHz)
Resolution 0.1%
Accuracy (5V logic) ±(2% + 10)
PW >10µs
Overload Protection 600VDC or 600VAC rms
Capacitance (MFD)
Range 5µF, 50µF, 500µF, 5mF
Resolution 1nF
Accuracy ±(3% + 15) 5µF, ±(3% + 5) 50µF to 500µF, ±(5% + 20) 5mF
Overload Protection 600VDC or 600VAC rms
Voltage DC (VDC)
Ranges 500mV, 5V, 50V, 500V, 600V
Resolution 0.1mV
Accuracy ±(0.5% + 2
Input impedance >100MΩ (500mV), 10MΩ (5V), 9.1MΩ (50V-600V)
Resistance (Ω)
Ranges 500Ω, 5kΩ, 50kΩ, 500kΩ, 5MΩ, 50MΩ
Resolution 0.1Ω
Overload Protection 600VDC or 600VAC rms
Accuracy ±(1.0% + 5) 500Ω to 500kΩ, ±(1.5% + 5) 5MΩ, ±(3.0% + 5) 50MΩ
Continuity
Range 500Ω
Accuracy 0.1Ω
Response time 100ms
Audible beep <30Ω
Overload Protection 600VDC or 600VAC rms
Diode Test
Test current 0.8mA (Approx.)
Accuracy ±(1.5% + 5)
Open circuit volts 3.2VDC typical
Audible beep <0.03V
Visual Indicator Green LED
Overload Protection 600VDC or 600VAC rms
Amps AC (AAC) True RMS
Ranges 50A, 400A
Resolution 0.01A
Crest factor ≤ 3
Accuracy ±(2.0% + 10) 50-60Hz
Jaw Opening 1.2in (30 mm)
Frequency (Hz) Through Clamp
Range 10Hz to 400Hz
Accuracy ±(0.1% + 5)
Minimum current range > 5AAC
Overload Protection 400AAC
Resolution 0.1Hz

Questions & Answers


There are no questions or answers for this item.